Per pre-authorized diagnosis, recharge rooftop package equipment. System is known to have leaks and there is no guarantees or warranties on refrigerant, labor, or additional diagnostics or trip charges Recharge 3.8 lb R422D (full charge) XP brand refrigerant leak stop with dye Pre recharge, The system was locked out on low pressure switch with 6.0 PSI Recharge equipment to running pressures of 70psi with 25° superheat and 399psi discharge pressure Supply temperature after recharge 60.6° f Equipment does not have any drain lines attached to assist in condensate removal Both 20x30x1 air filters had to be removed due to excessive air flow restriction