Water furnace 5 series Thermostat locked out on e10 compressor monitor with 31 lockout cycles recorded in AID diagnostics. Control circuit is active with power provided by EAH supply voltage Compressor circuit has no power. 45 amp two-pole breaker in the main panel is in the tripped off center position. Also at the same time One of the two five amp resettable circuit breaker at the control board is also tripped.. Both circuit breakers reset and all systems ran normal. E10 on the communicating thermostat was activated by no compressor power or operation. The primary cause of both circuit breaker trips could not be determined while on site today. 30uf compressor capacitor is within specs Hot water generator circuit is functioning and running normal. Two pump flow center is also functioning with both motors operational registering 15.5 GPM on the AIS tool System is registering high heat of rejection at 54K on aid compared to book specs however all other systems, water temperatures,