Performed cooling maintenance on a Daikin Fit air conditioning system Blower clean Filter is new Put alkaline tablets in the drain Wired condensate safety switch to the auxiliary alarm wire and enabled auxiliary alarm in the furnace settings Checked furnace for any signs of condensate leaks from heating season Put system into charge verification mode Condenser coil is clean Let system operate 20 minutes 22⁰ drop across evap coil 10⁰ liquid line subcooling System is running within factory specifications at this time.