Replaced 16x25x1 filter Compressor amps 5.9 Outdoor fan motor amps 0.9 Capacitor 36.14/5.83 under load measurements 23⁰ delta T (68 RAT 45 SAT) 36⁰ VSAT 12⁰SH 77⁰ LSAT 8⁰ SC Washed the condenser coil Checked wiring. All connections are secure and tight. No signs of overheating. Air conditioner is operating within factory specifications at this time. No concerns found.