Job Checkin

Electrical repair was completed, tested system Tested system in Cool Mode ( system uses two compressors ) both outdoor condenser fans are faulted. Fan #1 has open windings and will not energize, fan #2 has shorted windings. Refrigerant circuit #2 has a leak in the refrigerant circuit, refrigerant circuit #1 looked adequately charged but due to fans not working there is no way to fully know. Refrigerant circuits use a shared condensor and evaporator fin pack so if the refrigerant leak is discovered in the evaporator or condensor then both refrigerant circuits will have to have the refrigerant removed, the fin pack replaced and then both circuits vacuumed and recharged with refrigerant Tested system in Heat Mode; functions as designed Disconnect AC thermostat wire at unit control board so system can still heat