Job Checkin

Getting multiple error codes in history photo attached*, Homeowner stated turned to fan and then cool mode and then error codes activated. Switched to regular cool mode, getting fluctuating voltage 1-4V from e1, e2 to common on outdoor AC, with 27V at Red to common. Outdoor unit is operating properly. At zone board on damper getting 27V on Zone 1 Power open to common, (normal operation). At zone board on equipment side E1,E2 to common getting fluctuating voltage 1-4V. R-C 27V at zone board. Started up in Charge mode test, zone damper test, was unable to replicate code. Switched system off the to fan on then to cool and did not replicate code.system is likely having intermittent communication error, Unable to replicate faults, homeowner has concerns of system issue, also noted the gap space between filter door is not up to customer satisfaction, adding thicker foam tape will close gaps, homeowner noted filter is also dirty after 1 month after installation, informed typically is normal f