View visual findings from this job here - https://visionshare.xoi.io/?id=XA-57DC-7DDBCE354D2A4CD5891D2ABFF45BDE9E Preform maintenance on (2) zone heating w/ DHW Aulta High efficiency gas water boiler: * shut power to system * open boiler cabinet doors * removed flame rod and spark igniter: Cleaned with copper bristle brush, and polished with steel wool- Reinstalled and secured in place * Removed bottom of neutralizer trap and washed clean * Removed tube and flush condensate trap and prime with fresh water * Removed neutralizer condensate pump * Dump old minerals * Wash inside of condensate pump, clean and clear * Install new neutralizer minerals provided by customer * Reassemble and secure pump back in place and test operations multiple times to ensure no leaks- okay * Secured and inspected electrical wiring, Connections and components * Tested and inspected water feed/ Back flow, Expansion tank, Spiral vent and relief valve- okay * Confirm boiler pressure is normal * Cleaned out ins