View visual findings from this job here - https://visionshare.xoi.io/?id=XA-213F-A3B0C9773B8B4D56B49439CAD77D3710 Return to replace hot surface igniter for Lennox forced air gas furnace: * turn thermostat OFF which is satisfied at 72 degrees * shut power to furnace * removed furnace cabinet door * open burner cabinet inside furnace * disconnected electrical from existing igniter * removed existing igniter from furnace * installed Brand new gasket on brand new igniter hardware * installed Brand new hot surface igniter / gasket and all hardware into furnace * connect and secure electrical harness to new igniter and zip tie back with all electrical neat and clean * close up the burner cabinet and review all connections before returning power to system * call for heating from Ecobee thermostat: inducer motor is on, Pressure and limit switches closed, Igniter glows up gas valve opens and furnace fires- Blower motor is on and running-Normal operation * Monitor system for 10 minutes before