Return Visit to Reclaim Refrigerant & Check operation of TXV - Upon arrival found system running, Checked pressures 98psi over 258psi with Suction pressure below freezing. Outdoor ambient 68F. Checked indoor unit TXV, System is UNICO Model M4860CL1 - Bulb is mounted on Suction piping. Relocated Sensing Bulb, mounted and strapped to evaporator. Ran system and let run for 10 minutes, checked refrigerant pressures ok, checked delta T receiving good temperature split. Checked filter and return in living room ok. Cleaned out trap and flushed drain, tested condensation pump operational. Unit is fully operational and cooling well at this time. While on-site client mentioned that (3) UNICO Supply Vents are missing outlet screens. Will have the office contact client regarding pricing. Reviewed all work completed with client, emailed work summary. Follow up action: Return Visit to Install (3) UNICO Outlet Screens