Service call for no a/c in dance studio 2nd floor suite. On arrival thermostat was set to 67 but reading 83 degrees. Found a bad fuse at the outdoor disconnect for the condenser. This fused was replaced and system started up. Checked refrigerant pressures, total amps and compressor amps. Pressure are good and system is back up and running. It is recommended to replace the fused disconnect to a regular disconnect and also to upgrade the breaker for the outdoor condenser. The current fuse is a 30amp and the max fuse can go up to 45 double 208. It is possible that the fuse burned out due to the system needing a maintenance also the location of the outdoor condenser is under a deck and with hot temperatures this could drive up the amperage causing the fuse to blow out. System is in need of a maintenance the air handler is located downstairs in the growlers bar. An extension ladder is needed and also two technicians. The tenant needs to speak with the landlord so we can coordinate acces