(1) AC Maintenance - UNICO -Upon arrival client mentioned that she won’t be on site until 9am. Checked condenser pressures checked fuse found fuse blown, supplied and installed 30 amp fuse, checked electrical compartment and cleaned, found pitted contactor and out of range capacitor, Supplied and installed Turbo Capacitor and Contactor at condenser, also installed Hard Start Kit and removed potential relay. Checked indoor unit, flushed drain line, checked evaporator coils ok, filter recently replaced. Started system, checked delta T ok, performed full condenser wash to remove dirt and debris from coils. Unit is now fully operational and cooling well. Reviewed all work completed with client, collected payment, emailed invoice.