View visual findings from this job here - https://visionshare.xoi.io/?id=XA-AB08-B464EB80B5C343AC850B56A9CAD525A1 Perform maintenance on one Navion gas fired water boiler with two Hydro air, handlers and domestic hot water indirect tank: GAS WATER BOILER: low water cut off was just replaced and tested on system Remove the bottom of condensate trap Removing all dirty water from system, Cleaned cap and reinstalled securing in place Flushed and tested neutralizer kit and condensate pump- All water is flowing into pump- No leaks normal operations Neutralizer minerals in good condition with minimal wear Removed fresh air intake screen, Cleaned and reinstalled Removed flame rod and spark igniter- Showing extremely heavy wear and igniters are morphed- Replacement is highly recommended Vacuumed and dusted out inside of boiler cabinet and components Secured electrical wiring and connections Inspected inside of boiler cabinet for leaks or corrosion Test and check expansion tank, Water feed