Return to reclaim refrigerant, Repair leak on suction line at condenser, And full recommissioning: at arrival shut power to the system reclaim whatever remaining refrigerant was left inside the system remove core pins from service ports protect the suction line service valve in preparation for repair with torch, braze and repair leak at suction line outside preform nitrogen pressure test at 400psi on coil, line set and condenser check with bubbles to confirm no leaks and system holding at 400psi release all nitrogen from system place system into vacuum while system is in vacuum- removed panels of the condenser to expose the condenser coil- Coil and cabinet cabinets are dirty Chemically sprayed and washed outdoor condenser coil, Cabinets and fan blades, clean and clear Reassemble and secure all panels back onto condensing unit System and vacuum over one hour- holding install factory charge + additional for line set and coil totaling in 10lbs 9oz R410A cycle system on and off multiple t