450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for bowling green, va


Map of Bowling Green VA
James M.

James M.


Job Checkin

Upon arrival cleaned coil off and cleaned off blower. Indoor coil found no hits for leaks. Wires all tight. Found 5mfd capacitor at 2.6mfd, showing low. Let indoor run, went outside, capacitor checked out at 50/5 mfd. contacter is showing signs off pitting, fan motor has a small amount of oil next to the shaft. Coil is clear. Wires are tight. Fan amped at 1.5amps. Compressor amped at 6.8amps. Refrigerant Levels are 70/210. Compressor megohmed green. Spoke with customer about price to fix the system or if we should start looking at replacement. Customer explained she didn’t wanna fix it up because she knows in time it will need to be replaced. She did not want a manager to come out and give her a quote she wants to wait till the system fails.