(Attic system) The evaporator coil is clean and free of debris. All water safety’s are working properly at this time. The Reme halo is working properly at this time. The blower amps are 1.16 in correct range per manufacturer specifications. The emergency heat amps are 20 on both legs in correct range per manufacturer specifications. I cleared the ez trap and the condensate drain line is flowing properly at this time. All wiring is tight and in good condition. I cleaned the condenser coil. The run capacitor is in correct range per manufacturer specifications. The Contactor is in good condition. The refrigerant pressures are 270/130 in correct range per manufacturer specifications. The reversing valve is working properly at this time. Defrost is working properly. The compressor amps are 4.25 in correct range per manufacturer specifications. The condenser fan amps are .5 in correct range per manufacturer specifications. The system is working properly at this time. (Basement system)