Performed post install inspection of one heat pump system. Inspected blower assembly and evaporator coil for cleanliness, both are clean and free of debris. Blower motor is currently amping within range of manufacture specifications at 1.8. Tested emergency heat operation, both banks of emergency heat are operating properly and amping at 21.1/20.8. Electrical connections are tight with no broken or frayed wires. Cleared eztrap and confirmed drainage. Thermostat is operating properly. Confirmed all voltage is correct to the system. Checked over the heat pump side of system. Condenser coil is clean and free of debris. Condenser fan motor is currently amping within the range of manufacture specifications at 1.4. Compressor is also amping within range of manufacture specifications at 8.7. Electrical connections outside are tight with no broken or frayed wires. Contactor is in good condition with no pitting. Surge protector is still functioning as it should. Refrigerant pressures are with