450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for elkwood, va


Map of Elkwood VA
Hassan D.

Hassan D.


Job Checkin

Cooling inspection HP AHU Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Delta T 19 F degrees Inspected evaporator coil , coil is clean and free of debris at this time. Performed complementary leak search, no leaks found at this time. Return temp 70F , supply temp 51F inspected blower motor, housing and wheel, all is clean and working properly at this time Motor is spinning freely at this time Blower motor amp draw, 0.45 amps Inspected cabinet for cleanliness, cabinet is clean at this time. Clear drain line, drain is clean at this time. Inspected and air filter filter is ok at this time. HP Inspected high and low-voltage wiring, all electrical wiring is intact and tight at this time. Inspected 0FM, motor is spinning freely and operating properly at this time. OFM amp draw , 0.52 amps Inspected run capacitor 35/5 -/+6%, capacitor is working out of range at this time. Readings Herms 30 uF , Fan 2.7 uF Dual run capacitor needs to be