Upon inspection found: Condenser coil dirty. Compressor pulling 9.5 amps this is the maximum amp draw per manufacturer Mega ohm compressor compressor is bad . System is a little bit low on refrigerant R22. Run capacitor is operating out of manufacturer rage. System is operating but it it prone to failure at anytime due to the state of the compressor and system as a whole.