Inspected the unit over again found that the intake side was dirty. Pulled coil as far as technician could get it and cleaned it. Brushed it up and vacuumed inside the return box. The blower wheel end housing is clean. The blower motor amped in @1.14 which is within the manufacture specifications. The AUX heat is currently operational at this time of the inspection. Both bars amped in @19.00 and @17.66 which both of these are within the manufacture specifications. Inspected the outtake side of the coil and it was clean. The pan was clear. The trap was clear. All Safeties are operational at this time of inspection. Overall this system is clean and operating properly at this time of the inspection. Outdoor- Inspected all wiring connections, everything is clean and secure at this time. Inspected the ODF, it is spinning freely at this time. The ODF amped in @.63 which is within the manufacture specifications. The compressor is operating properly at this time. The compressor amped in