Inspection of system Basement indoor Inspected blower wheel and evap coil both clean and free of debris, inspected electrical wiring and connections none found burned are broken at this time, inspected blower motor amps .47 in range per manufacturer specs, inspected condensation drain brushed out and tested all working good also checked condensation pump tested it worked well at this time, inspected filter all clean free of debris inspected t-stat operations all working good at this time. Basement heat pump Inspected condenser coil it was alittle dusty, cleaned off with just water coil is very clean at this time, inspected electrical wiring and connections none found burned are broken at this time, inspected contactor very little pitting at this time. Inspected capacitor 35/5 it was bad under warrenty got approval from home owner to change out, inspected compressor amps 5.56 in range per manufacturer specs, inspected outdoor fan amps .80 in range per manufacturer specs, inspe