450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for lake of the woods, va


Map of Lake of the Woods VA
Hassan D.

Hassan D.


Job Checkin

Heating inspection AHU Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected his trips, heat strips are pulling 20 Amps at this time inspected blower motor, housing and wheel, all is clean and working properly at this time Motor is spinning freely at this time Inspected cabinet for cleanliness, cabinet is clean at this time. Clear drain line, drain is clean at this time. Inspected and replaced air filter (1) 20 x 20 x 1 filter is new at this time. HP Inspected high and low-voltage wiring, all electrical wiring is intact and tight at this time. Inspected 0FM, motor is spinning freely and operating properly at this time. Inspected run capacitor 45/5 -/+6%, capacitor is working within range at this time. Inspected HP coil , coil is clean and free of debris at this time . Inspected defrost mode, defrost is working properly at this time. Inspected compressor, compressor is working properly at this time. Checked Refrigerant pressure