Cooling inspection 1 system Crawlspace indoor Inspected evaporator coil it is clean and free of debris. Inspected blower wheel all clean and free of debris, inspected electrical wiring high and low voltage all in good shape none found burned are broken at this time, inspected blower amps .78 in range per manufacturer specs, inspected condensation drain brushed out and tested all working good at this time, inspected condensation pump tested all working good at this time, inspected filters all clean. Inspected t-stat operations all working good at this time, Crawlspace heat pump Inspected condenser coil it was alittle dusty cleaned off per maintenance contract, inspected contactor has alittle piting but not to bad to replace yet will keep a eye on during the maintenance, inspected capacitor 40/5 was reading 39.65/5.0 all in range per manufacturer specs, inspected compressor amps 6.56 in range per manufacturer specs, inspected condenser fan motor amps .90 in r age per manufactur