. Upon arrival customer stated his ac isn’t working. Went to indoor unit. The blower was running. The blower is clean. All wiring is good and tight. Had a call for ac. The blower motor amped at 1.32. The drain is clear. The drain safeties are working properly. The evaporator coil is clean. No leaks at this time. Jumped the heat out and it’s working properly at this time. Went to outdoor unit and found the fan was running but no compressor. Found capacitor bad. 45/5 reading 7/4. Customer had a parts warranty but no labor. Quoted everything up and went over it with the customer. He wants only the repair and thinks he has some kind of warranty with the builder since it’s a new house. He approved the labor. I installed the new capacitor. The system came on. The compressor amped at 5.73. The condenser fan motor amped at .59. Both are in rnshe. The Refrigerant pressures were 100/250. The system is working properly at this time.