Upon m arrival customer explained how system wasn't cooling. When going to the indoor unit found the coil iced up. At this point turned just fan coil thawed proceeded to leak search coil at this time no leaks were found. Inspected capacitor for the blower motor which was operating properly at this time. Leak searched outdoor unit no leaks detected at this time. Capacitor is weak still passing manufacture specification at this time. Standing pressures were above 200 psi. Provided customer options which customer accepted membership and refrigerant to system. Would like to come back out for invite back in 2 weeks to check on the pressures. System discharging 49 degree air on 73 degrees in the home.