. Upon arrival found thermostat set to 70 and it was 80 in the house. Went to indoor unit. Everything was clean. The blower was running. Went to outdoor unit. Had 24 volts for cool. Had no high voltage. Found 30 amp breaker in the sub panel tripped. Turned the breaker back on. System ran good for 45 minutes. The compressor was amping at 10.09. The condenser fan motor was at .57. The contactor is clean and free of pitting. The capacitor checked out good. All wiring is good and tight. The Refrigerant pressures were 125/250. 8.4 degrees of super heat. The breaker has warmer than the other ones. Need to get pricing on 30 amp breaker. Signed the customer up for membership.