Hassan D.

Hassan D.


Job Checkin

Cooling inspection HP AHU Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected evaporator coil , coil is clean and free of debris at this time. inspected blower motor, housing and wheel, all is clean and working properly at this time Motor is spinning freely at this time Inspected cabinet for cleanliness, cabinet is clean at this time. Clear drain line, drain is clean at this time. Inspected air filter, air filters are ok at this time. HP Inspected high and low-voltage wiring, all electrical wiring is intact and tight at this time. Inspected 0FM,OFM seals are broken and oil leaked out this motor is prone to failure at anytime. Condenser fan motor needs to be replace. Inspected run capacitor 45/5 -/+6%, capacitor is working out of manufacturer specs at this time. Dual run capacitor needs to be replaced to avoid system failure Inspected defrost mode, defrost is working properly at this time. Inspected condenser coil, condenser