Job Checkin

The customer requested to inspect only the outdoor unit. Heat pump. The condenser coil is clean and free of debris. The 40/5 run capacitor is weak on the herm and fan. The condenser fan amps are .29 in correct range per manufacturer specifications. The compressor amps are 6.72 in correct range per manufacturer specifications. The contactor is in good condition. The refrigerant pressures are 280/135 off a little due to rain but in correct range per manufacturer specifications. The wiring is tight and free of damage. The system is working properly at this time. I received permission for repairs. I replaced the 40/5 run capacitor. The customer signed up for our basic one system Club Membership. The customer requests a paper copy of today’s invoice.