The customer requested checking only the outdoor. The condenser coil is clean and free of debris. The condenser fan amps are .37 in correct range per manufacturer specifications. The run capacitor is in correct range per manufacturer specifications. The compressor amps are 6.49 in correct range per manufacturer specifications. The contactor is in good condition. All wiring is tight and free of damage. The defrost cycle is working properly at this time. The refrigerant pressures are 370/130 in correct range per manufacturer specifications. The system is working properly at this time. The customer requested a paper copy of today’s visit.