450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for port royal, va


Map of Port Royal VA
Hassan D.

Hassan D.


Job Checkin

Heating inspection AHU (crawl space) Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected heat strips, heat strips are pulling 19 amps at this time. Inspected blower motor, housing and wheel. Motor is spinning freely at this time. housing and wheel are clean at this time. Inspected cabinet for cleanness, cabinet is clean at this time. Cleared drain line, drain is clean at this time. Inspected air filter (1) 20X20X1 filter is clean at this time. H/P Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected OFM, motor is spinning freely and operating properly at this time. Inspected run capacitors 70 -/+5% and 7.5 uF -/+5%capacitor is working within range at this time. Inspected defrost mode, defrost is working properly at this time. Inspected compressor, compressor is working properly at this time. Checked refrigerant pressures and temperatures 386/120 and 157/91 Cycled system on h