Jeremy S.

Jeremy S. Job Checkin

All wiring is tight and in good condition. I completed a complimentary refrigerant leak search on the system. No leaks found at this time. I found the uv bulb is bad in the Photomax we just installed this year. I replaced the bulb. The refrigerant pressures are in correct range per manufacturer specifications. The furnace is in good condition and working properly at this time. The heat exchanger is in good condition. The system is working properly at this time. I completed our check sheet and emailed it to the customer. The customer declined options at this time.


Jeremy S.

Jeremy S. Job Checkin

I found the coils and blower wheels dirty in all three heads. The system is low on refrigerant. I completed a complimentary refrigerant leak search on the system. No leaks found at this time. The system needs to be charged after the heads are cleaned to obtain accurate pressures. The customer signed for repairs.


Dakota H.

Dakota H. Job Checkin


Trey M.

Trey M. Job Checkin

During my inspection, I found a few things that the customer needed to be aware of these included a drain pan strip for the primary drain pan of the system, because the drain pan was dirty and causing the drain line to accumulate buildup. I gave the customer the option to do this and he excepted and then found that the outdoor unit was not equipped with a surge protector. Customer did not accept at this time customer then explain to me that he was interested in the UV light. I talk to him about a UV photo max and he excepted that as well, at this time all equipment is performing well and all repairs are completed


Jeremy S.

Jeremy S. Job Checkin

All wiring is tight and in good condition. I cleaned the condenser coil. I found the suction line insulation falling apart. I completed our check sheet and emailed it to the customer. The system is working properly at this time. I installed a new surge protector in the outdoor unit. I cleaned the dryer vent. I replaced the lineset insulation at the outdoor unit.


James M.

James M. Job Checkin

Upon arrival spoke with customer and asked about and questions or concerns, he asked about the swing mode on the systems, we talked about how it works. Then he explained one night the systems felt like they where blowing out cold air, he said unit was saying DF, I explained if it goes threw defrost it will have DF on the face showing it is working properly and going threw defrost. Went threw, indoor units, both downstairs filters are clean. Coils are clean. Wires are tight. Blowers look good. Went upstairs, filter is clean, coil is clean but blower wheel is dirty. Went outside with system running, coil is dirty, wires are tight. Pressures are 135/374. System is working but recommend coil cleanings, and a membership. Spoke with customer, customer did not want membership with cleaning at this time.


Mike  M.

Mike M. Job Checkin

Preformed heating maintenance on heat pump system. Confirmed filters were clean and the thermostat is working properly. Checked electric heat strips and found amp draw within manufacturer specs 40.4 Took amp draw on blower motor and found within spec .94 Confirmed all high and low voltage was good and tight. Found blower wheel with slight build up, cleaned per contract. Evaporator coil is leak free and clean of any debris at this time. Cleared main drain and confirmed safety switches working properly. Took amp draw on the compressor and found within manufacturer spec 15.4 Checked amp draw on condenser fan motor and found within spec .62 Checked refrigerant levels and found within spec using heat curve chart 110/410 put system into defrost and found operating properly at this time. Returned to service


Mike  M.

Mike M. Job Checkin

Arrived at the home and spoke with customer about issue with his heat pump. Found 1 leg of high voltage melted at wire nut due to loose connections from lack of maintenance. Made high voltage repair turned power back on and now have 245v at transformer with 24v out. Found low voltage fuse blown after inspection of low voltage wiring found common wire rubbed up against cabinet in outdoor unit. Correctly tied up all wiring installed new fuse an now have a fully operating system. Verified operation in heating mode and returned to service gave customer multiple options for todays repair.


Loving Air Inc. .

Loving Air Inc. . Job Checkin


Loving Air Inc. .

Loving Air Inc. . Job Checkin

performed inpection and found out door system not operating due to failed compressor and pitted contactor.. System is 23 years old with R22 refrigerant which is unavailable… Also found breaker to system tripped due to power fluctuations to system.. Based on the age and condition and also refrigerant I recommended to customer to look and the possibility of replacement.. Appointment has been set for Tuesday September 6th between 1 and 4 pm.


Trey M.

Trey M. Job Checkin

** During my inspection the customer told me that the system was blowing air but it just wasn’t cold air. I went to the outdoor unit where I found that the compressor was not running. Upon further inspection I found that the 45/5 capacitor was popped. I told the customer in order to get the system back up and running we would have to replace this part. The system is only eight years old so I looked up the warranty on the system but it only had a five-year manufactures warranty. I then informed customer that it would be best if he got on the maintenance plan and in order to do that we would have to clean both the indoor and outdoor coils to get them up to manufacture specifications he agreed so I did the work. *** Maintenance: indoor unit: when I went inside to check the indoor unit I looked at the cleanliness of the indoor coil and indoor evaporator fan Motor/wheel and found that the evaporator coil was dirty and the indoor evaporator fan motor/wheel was not. I informed the customer


Cameron S.

Cameron S. Job Checkin

. Upon arrival filters were clean. Set thermostat to ac and went to indoor unit. The coil is clean. Coil has been replaced before. No leaks. The blower housing is clean. The blower motor amped within the manufacture specifications at 1.11. Inspected low and high voltage wiring. All wiring is good and tight. Drain is clear. Thermostat is operating properly. Went to outdoor unit. The condenser coil is clean. The compressor amped at 6.99. The condenser fan motor is spinning freely and amped within the manufacture specifications at .64. The capacitor checked out in range. The contactor is new and free of pitting. The disconnect is working properly. Inspected low and high voltage wiring. All wiring and wiring connections on outdoor unit are good and tight. The Refrigerant pressures are 125/280. The Refrigerant pressures are within the manufacture specifications. Leak searched outdoor unit and didn’t find any leaks. System is working properly at this time. No issues found. Quoted a surge p


James M.

James M. Job Checkin

Upon arrival customer explained system did not run. Customer explained he wanted to see what it would take to get a new system and get the duct work straight to keep the whole house warm. There is 2 3 registers upstairs, and 2 downstairs. Only 1 return by the stairs. An old electric heat system in the crawl. There is duct in the crawl. Called for a manager to come out and take a look, Rick is coming out. Rick came out and looked at everything and is going to speak wi5h the home owner


chrisw@lovingairinc.com

chrisw@lovingairinc.com Job Checkin

Performed post install inspection on one mini splits system with three heads. Front left head, evaporator is clean and free of debris. Removed filter an cleaned. Electrical connections are tight with no broken or frayed wires. Blower wheel is clean and free of debris. Gathered temperatures on return and supply, system has correct delta T. Right side head, evaporator is clean and free of debris. Removed and cleaned filters. All electrical connections are tight with no broken or frayed wires. Blower assembly is clean and free of debris. Delta T is within the correct range. Upstairs head, upon inspection of the unit had a smell of burning. Shut off breaker to the system and found the control board has a short and has burnt the board. Ordered the board through Carrier under warranty. Board is 3-5 days out. Will need to return and install the new board and test it’s operation. Carrier M#40MBFQ18- - -301- - S#5120V20024. Condenser coil is clean and free of debris. Condenser fan motor is


Cameron S.

Cameron S. Job Checkin

. Upon arrival went to indoor unit. The aux heat is working properly and amped at 19.98 and 19.99. Both are within the manufacture specifications. The blower housing is clean. The blower motor is spinning properly and amped within the manufacture specifications. The evaporator coil is very clean. Leak searched coil and found no leaks at this time. Cleared drain line. Inspected low and high voltage wiring. All wiring is good and tight. Went to outdoor unit. The Refrigerant pressures are 135/360. The condenser coil is clean. The compressor amped at 13.87. The condenser fan motor amped at .68. Both are within the manufacture specifications. The capacitor checked out in range. The contactor has some burn marks on it. Quoted to replace it due to burn marks and to prevent any future problems. Inspected low and high voltage wiring. All wiring is good and tight at this time. System checked out ok at this time. Recommend replacing contactor.