The furnace is level and sealed air tight. The evaporator coil is clean and free of debris. The blower amps are 8.65 in correct range per manufacturer specifications. I reinforced the armaflex at the evaporator coil. The inducer motor amps are .94 in correct range per manufacturer specifications. The wheel on the inducer has come off the shaft. I reattached the wheel and tested operation. If it comes off again a new warranty inducer motor will need to be ordered and installed. The flame sensor and igniter are in good condition. The gas valve is working properly at this time and pressures are in correct range per manufacturer specifications 3.6. All wiring is tight and in good condition. The condenser coil is dirty. Recommend cleaning to prevent component burn out. The compressor amps are 6.37 in correct range per manufacturer specifications. The condenser fan amps are .65 in correct range per manufacturer specifications. The refrigerant pressures are 303/135 a little off due to dirty