The evaporator coil is clean and free of debris. The blower is clean and amps are 7.64 in correct range per manufacturer specifications. The condensate drain is clear and flowing properly. All wiring is tight and in good condition. The compressor amps are 8.99 in correct range per manufacturer specifications. I cleaned the condenser coil. The condenser fan amps are .72 in correct range per manufacturer specifications. The refrigerant pressures are 250/112 in correct range per manufacturer specifications. (69 outside)(65 inside). The contactor is in good condition. The 45/5 run capacitor is in correct range per manufacturer specifications. Recommend an ez trap for the primary water safety on the furnace and insulating the suction line at the evaporator coil. The system is working properly at this time. The customer declined recommendations at this time but may schedule them for the end of the month.