No A/C, outdoor fan running but not the pumping system, checked and found that the outdoor voltage enhancement system had failed factory spec 30/5, actual 0/4.1, replaced and test ran, compressor run load amps factory spec 12.4, actual 8.3, outdoor fan full load amps factory spec 1.5, actual 1.3, operation normal at this time, do not recommend any other repairs due to the age and obsolete coolant. WO-TNFR176803