Performed AC club rejuvenation cleaning Checked indoor voltage enhancement factory specs 15uf actual 14uf. Air movement system factory specs 9.3amps actual 3.66amps. Air movement blower wheel is clean. Heat transfer media coil system was dirty , cleaned coil. Air filter is dirty customer will change. Checked all electrical wiring connectors and harness are tight and secured Delta T 20 degrees. Cleaned condenser coil. Refrigerant pumping system RLA 17.9amps actual 8.38amps outdoor air movement system factory specs 1.50amps actual 1.27amps. Voltage enhancement system factory specs 45/5uf actual 44/4.89uf Voltage gateway is good res of 18.1 checked all electrical wiring connectors and harness are tight and secured system is functioning as intended at this time. System is up and operational at the end of cleaning.