1638 Elkton Road
Elkton, MD 21921
410-392-9350

Local Reviews
for garnet valley, pa


Job Locations
for garnet valley, pa

kozemchakmoonservices@gmail.com

kozemchakmoonservices@gmail.com Job Checkin

Club rejuvenation gas warm air. Filter clean, blower a bit dirty, cleaned with brush, heat exchanger pass, checked for gas leaks with detector, no leaks detected, checked coil for leaks with detector, no leaks detected. Inlet pressure 9.8 inWC, outlet pressure 8 inWC, inducer 1.04 inWC, flame sensor .38 inWC, indoor fan 3.8 inWC, indoor voltage enhancement system 9uf rated for 10uf, and Delta was 35. System running under normal conditions at this time.


Kyle H.

Kyle H. Job Checkin

Washed off air filter. Supply temp is 48 degrees with a return of 68. Delta T is 20 degrees. Air circulation system is clean. All electrical connections are tight. Wiped out dust from system. Flushed water removal system with water and is draining properly. Indoor voltage enhancement system has a factory spec of 10uf and reads 10mfd and is within factory spec. Did leak search on indoor heat transfer system and found no leaks. RLA and FLA are within factory spec on the outdoor system. Cleaned off the back of the heat transfer system. Outdoor voltage enhancement system has a factory spec of 45/5uf and reads 44.4/4.8mfd and is within the allowable fault. Voltage gateway is without any pitting or burn marks. Wd40 wipedown on the indoor and outdoor systems. All systems running well at this time.