Condenser not running due to minor high voltage electrical fire burning out wire connectors on the power supply Install two replacement power supplies one for compressor and one for fan motor Replace burned wiring 370vav 35uf 370vac 4uf Pull top of equipment to replace burned wiring Run test cooling refrigerant pressures after repairs 61\213 with 60.2 supply temperature Lock mechanical room door lock front door, thermostat set to cooling mode at 68