2018 Trane running but not cooling upon arrival Indoor inspection appears normal air filter is good system is calling for cooling one at 2000 CFM Outdoor unit fan is running but no compressor operation Discovered burned out compressor power supply and under the specs fan motor power supply Combined both power supplies into one turbo 200X set at 440 volts 80 + 7.5 uf Clean condenser coils and drain ports