Upon arrival, system is in off mode. Turned thermostat to cool and down to 65 to ensure operation. Inspection if indoor unit shows that blower is running. While down there, for approximately 1 second, with a 10 second pause, a vibrating noise can be heard. Inspection of outdoor unit shows that the fan is running, but the compressor is not. The noise being heard is the compressor attempting to run. Tested 50/5uf capacitor at 14/4.9uf. Capacitor is way out of range on the compressor leg, directly preventing the compressor from operating. Installed new 50/5uf capacitor for testing. With new capacitor installed, system came on as it should. Fan and compressor are both operational. Did not check refrigerant as there is no issues suspected at this time. System is operational in cooling at this time. Contacted Goodman for parts warranty status. Goodman says equipment was not registered and the 5yr parts warranty eneded in June of 2025. New capacitor comes with 1 year parts warranty and 30 day