725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Job Locations
for lewis center, oh


Map of Lewis Center OH
seth p.

seth p.


Job Checkin

Upon arrival the system was running in cooling mode and set to 73 and shortly after arrival shut off due to a satisfied thermostat. Initial inspection of all the equipment discovers that all equipment in the basement is running in very good condition including a replacement 3\4hp blower by a third party. And with a clean 16x25X1 pleated air filter Blower dip switches are set to 4 ton with a matching 3 ton ac 15 seer ac system validating maximum blower speed for maximum air volume on the second floor. No additional blower volume or speed is available for this system. As is the equipment is producing 52° supply temperature in the basement. Outdoor equipment inspection discovers a heavily matted condenser coil but still nearly perfect running refrigerant pressures under today's conditions. Replacement turbo 200 capacitor is good Water flush condenser coil and return all equipment to normal service and settings. *** To even out temperatures throughout the house especially from Floor t