Second floor water leak inspection Disassemble front panels of air handler for full access to the evaporator coil and drain pan. Visual inspection confirms no blockages or debris anywhere in the drain system at the second floor level. Freshwater flush second floor 3/4pvc drain system and drain trap with 5 gallons freshwater to confirm no leaks Run test cooling mode at 51° supply temperature Coil condensation confirms full refrigerant levels Basement split Geo system is running in fair to good condition however ground loop water pressure was at 5:00 PSI and one of two flow center pumps is still non-functional. Repressurize ground loops for second floor system from 5 to 42psi, maximum house water pressure at new hot water tank