10-11am perry 252 671 4290 meeting you Kitchen Suppression Inspection Ansul R102 1.5 Gallon Kitchen: Semi-Annual Kitchen System Inspection Inoperable Deficiency for Ansul R102 1.5 Gallon Kitchen: Ansul 1.5 gallon: system upgrade needed ** Ansul 1.5 gallon Improper coverage above ranges 6 burner and 10 burner range lacks protection. **6 burner range is half way outside of the hood.** **U shaped detectors being used, stainless steel (3) V shape scissor clips need to be installed.** UL-300 upgrade needed Loose wiring inside ottoman (Junction box needs to be installed) **Shock hazard** 1/4 piping through out the system