Dwayne  B.

Dwayne B.


Job Checkin

tom 1230 see tom cell 410-404-1591 meeting you Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) RANGEGUARD 4 GAL Alarm Int: No Inoperable Deficiency for RangeGuard Unknown 4 Gallon Back wall by dish washer: Same deficiency’s remain from last inspection: Range Guard 4 Gallon 4 gallon cylinder is due for hydro testing MFD ( 8 burner range, 2 burner/ flat top griddle, Grill and fryer lacks detection and protection. System lacks gas shut-off gas valve frozen with heavy grease. No local bell interlock. **UL-300 upgrade needed** Deficiency for 5 ABC End of bar: 5lb abc extinguisher located at the end of the bar is due for hydro testing. Last 6 year maintenance was performed in 2013.