7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for waldorf, md


Map of Waldorf MD
Dwayne  B.

Dwayne B.


Job Checkin

9+6 gal ansul adam/9am Kitchen Suppression Inspection KITCHEN SYSTEM INSPECTION SEMI ANNUAL Deficiency: Ansul 9 gallon 2 out 3 cylinder are due for hydro testing (MFD 2006x2) Deficiency: Ansul 6 gallon 1 out of 2 cylinders are due for hydro testing (MFD 2006) Inoperable Deficiency: Ansul 9 gallon Detection line failed Parts needed: 7 detectors 30ft conduit 30ft cable 2-3 hours labor Inoperable Deficiency: Ansul 6 gallon Detection line failed (Pre UL-300) U shaped clips obsolete Parts needed: 4 Ansul detectors 15ft conduit 15ft cable 1-2 hours labor Deficiency: Ansul 6 gallon Pre UL-300 nozzles in duct and plenum 2 (1n nozzles need to be installed 2 (1w nozzles need to be installed Deficiency: Ansul 9 gallon Pre UL-300 duct and plenum nozzles 4 (1n nozzles need to be installed 4 (1w nozzles need to be installed Inoperable Deficiency: Chemical found in suppression lines, both Ansul 9 and Ansul 6 needs to be flushed and purged with nitrogen