Arrived to no cool, found breaker turned off causing no power to upstairs unit, found faulty sequencer in place of fan control relay however we did not have a fan control relay so we used a contactor. Homeowner is fully aware that heat strips will not work causing unit to not heat at full capacity. System is now cooling properly with a 22* temp split, a saturation temp of 41 and superheat of 2.