View visual findings from this job here - https://visionshare.xoi.io/?id=XA-7C6F-268D800BAF164E10A9CF33D3229A10C3 Customer has no heat and no hot water: At arrival, check boiler and found the Argo panel calling for domestic hot water The boiler display screen is flashing red There is a lockout for ignition failure Shut power down to the boiler Remove the flame sensor and spark igniter from the system- Both showing heavy ware Cleaned both components up with copper bristle brush, and reinstalled Both casing for the electrodes are deteriorated and broken- Wiring For spark igniter and flame sensor replacement Recommend Confirm that the condensate trap was not blocked up and water is draining Neutralizer minerals are in bad shape and should be replaced The inside of the cabinet is showing heavy corrosion on most components Return power to boiler and test system operations: Immediately you can hear the blower motor on the system, grinding and not working properly- System fails to fire The