Job Checkin

View visual findings from this job here - https://visionshare.xoi.io/?id=XA-90AE-D80616A7318A43ADB3B1B348DF310C7F Customer has no heating in the home: * Confirm that nest thermostat is calling for heat set for 80° * Check gas furnace in basement- System is off * Found the control board showing an error code of three red flashes indicating an issue with the venting on the furnace * Confirm that both of fresh air and flu piping are clean and clear on the furnace * Started a case with the manufacturer tech-support : Case number 12459256 * After reviewing diagnostics with manufacturer, found that the pressure transducer Is not reading the correct DC voltage- When it should be reading zero it is reading 1.004 DC v * When the wire harness for the pressure transducer is removed / The fault cleared and a call for heating is placed the inducer motor does turn on But the system falls back out because the pressure transducer is no longer in the loop * There is no way to bypass this pressure tr