Heat rise for attic system is 30 degrees. Changed air filter. Static pressure .41 inWC. Indoor and outdoor coils are clean. Coils have no refrigerant leaks. Compressor amps read 15.2 amps. rated 22.1 amps and is good. Outdoor fan amps reads 1.3 and is rated for 1.8 and is good. Indoor voltage enhancement system rated 20uf actual is 19.3 uf and is within the allowable fault. Performed leak search. Outdoor voltage enhancement system rated 75/10uf actual is 80/9.7uf and is not within factory spec or the allowable fault range. Recommend replacing voltage enhancement system as this can cause high amperage to occur casing more wear and tear on the outdoor motors. 1st and 2nd floor systems have a .4inWC static pressure. Compressors are good at 1000 megaohms. All indoor fans are clean. Auxiliary heat systems are working properly. Coils have no leaks. All electrical connections are tight. Put foam tape on outdoor unit for 1st floor system to stop the aluminum fins on the coil from s