Checked all ac units. 1st floor getting a 18 degree delta t. 2nd floor unit 20 degree delta t. 3rd floor 21 degree delta t. Changed filter on 3rd floor. All others filters customer recently changed and look fine. All evaporator and blower wheels are clean eletrical connections are tight Checked all drainlines cleared drainline for 3rd floor. Checked all voltage enhancement systems and gateways voltage enhancement system for 3rd floor is pitted And voltage enhancement system for voltage enhancement system read below factory specs actual 30 vs factory spec 35uf. Vhsnged voltage enhancement system and voltage gateway All units are working at this time WO-TNFR153813