1638 Elkton Road
Elkton, MD 21921
410-392-9350

Job Locations
for bel air, md


Map of Bel Air MD
Jack W.

Jack W.


Job Checkin

Ac club rejuvenation: the supply temperature was 39 degrees and the return temperature was 68 degrees. The delta T had a temperature difference of 29 degrees. Checked air filter system, which was clean and clear of all debris because customer changes out. Checked air movement system, which was clean and clear of all debris with no signs of concern or worry. Checked all wiring inside electrical compartment, which were all clean and secure. Checked drain line system, which was clean and clear of all debris with no signs of concern. Cleaned inside and outside of indoor unit with proper cleaner and wipes. Checked outdoor voltage enhancement system, which was running at a 44.8/9.9uf. Factory spec is a 45/10uf so it was running within the allowable fault of the system. Checked outdoor voltage gateway system, which was clean and clear of all debris with no signs of concern or worry. Cleaned off inside and outside of outdoor unit with proper cleaner and wipes. System is up and running at norma