Confirmed locked up compressor pulling 98 amps with replacement capacitor and super boost installed Compressor, compressor capacitor, liquid line filter dryer, TXV, 81 Oz new r410a all need to be replace. Air coil needs duct board dropped removed for heavy duty shop vac and chemical coil cleaning, pressurized ground loop system contains alcohol and both pumps are confirmed operational however pressure has been reduced to below 10 psi. Ground loops need repressurized with house water pressure. Refrigerant pressure is holding at 210 PSI indicating a probably mostly sealed system however due to the nature of the compressor mechanical lockout all refrigerant needs replaced including a acid scavenger treatment Seth will follow up with parts distributor and prepare estimate ASAP